PQLite with harmonics & transient capture: This TASKCard is designated with a /H/T and changes the 4300 to a full featured power quality monitor so that it can record sags, swells, outages, demand, energy, harmonics, and voltage and current transients as short as one microsecond.
Memory card functions: Versions of the TASKCard are available with memory card functions, which allow you to save data to an optional memory card manually, automatically, or both.
Operational Description
Scope Mode
Functions as an oscilloscope, displaying real-time waveforms of voltage and current for all channels.
Meter Mode
Provides the functions of a true RMS voltmeter and true RMS clamp-on ammeter. Can also display voltage and current phasors for all of the channels.
Monitoring Capacity
Can monitor any of the following power configurations:
Single phase, 2 wire
Split phase, 3 wire
3 phase, 3 wire ( delta )
3 phase, 4 wire (wye )
While monitoring any of the above configurations ( except delta ), the 4300 can also be connected to monitor neutral to ground voltage and neutral or ground current.