AC Current clamp for measurements on power systems for power quality measurements and distribution system troubleshooting.
The probe is compatible with oscilloscope inputs and provides a millivolt output signal to allow an oscilloscope to accurately reproduce current waveforms with minimal distortion. Double and reinforced insulation throughout protects the user from working voltages of up to 600V rms. The jaw size allows measurements on large power cable assemblies as well as on individual wires. The 100 kHz low pass output filter eliminates wideband noise.
Usable Freq. Range (with Current Derating): 5 Hz..100 kHz
Required Instrument Input Impedance: > 1 Mohm // =<47 pF
Maximum Conductor Size: 54 mm (2.13")
Working Voltage: Clamp jaws to ground 600V rms. CAT III per IEC 1010-02-032
Float Voltage: Output cable and connector to ground circuits 600Vrms CAT III per IEC 1010-02-032